> For the complete documentation index, see [llms.txt](https://grid-exchange-fabric.gitbook.io/gxf/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://grid-exchange-fabric.gitbook.io/gxf/protocols/iec61850/swdevice-010805/setlight.md).

# SetLight

## Description

Request which commands the device to switch on or off one or several light relays. If optional value 'index' is omitted, all relays configured as light are switched. In that case, the message will contain exactly one LightValue and all relays will switch to that LightValue. In case the value 'index' is included, multiple instances of LightValue can be used (up to 6), each indicating a particular relay.

Response which returns the result of the request.

## IEC61850 Fields

| **ATTRIBUTE** | **FC** | **SUB ATTRIBUTE** | **DATATYPE** | **DESCRIPTION**                                              |
| ------------- | ------ | ----------------- | ------------ | ------------------------------------------------------------ |
| XSWC2.Pos     | CO     | Oper.ctlVal       | BOOLEAN      | Flag which, if set to true, immediately switches relay 2 on. |
| XSWC3.Pos     | CO     | Oper.ctlVal       | BOOLEAN      | Flag which, if set to true, immediately switches relay 3 on. |
| XSWC4.Pos     | CO     | Oper.ctlVal       | BOOLEAN      | Flag which, if set to true, immediately switches relay 4 on. |

## Example

Soap requests and responses sent to and from platform:

```markup
<soapenv:Envelope
    xmlns:soapenv="http://schemas.xmlsoap.org/soap/envelope/"
    xmlns:ns="http://www.opensmartgridplatform.org/schemas/common/2014/10"
    xmlns:ns1="http://www.opensmartgridplatform.org/schemas/publiclighting/adhocmanagement/2014/10">
   <soapenv:Header>
      <ns:ApplicationName>SoapUI</ns:ApplicationName>
      <ns:UserName>Sander</ns:UserName>
      <ns:OrganisationIdentification>LianderNetManagement</ns:OrganisationIdentification>
   </soapenv:Header>
   <soapenv:Body>
      <ns1:SetLightRequest>
         <ns1:DeviceIdentification>KAI-0000000053</ns1:DeviceIdentification>
         <ns1:LightValue>
            <ns1:On>true</ns1:On>
         </ns1:LightValue>
      </ns1:SetLightRequest>
   </soapenv:Body>
</soapenv:Envelope>

<SOAP-ENV:Envelope
    xmlns:SOAP-ENV="http://schemas.xmlsoap.org/soap/envelope/">
   <SOAP-ENV:Header/>
   <SOAP-ENV:Body>
      <ns2:SetLightAsyncResponse
          xmlns:ns2="http://www.opensmartgridplatform.org/schemas/publiclighting/adhocmanagement/2014/10"
          xmlns:ns3="http://www.opensmartgridplatform.org/schemas/common/2014/10">
         <ns2:AsyncResponse>
            <ns3:CorrelationUid>LianderNetManagement|||KAI-0000000053|||20180925093054301</ns3:CorrelationUid>
            <ns3:DeviceId>KAI-0000000053</ns3:DeviceId>
         </ns2:AsyncResponse>
      </ns2:SetLightAsyncResponse>
   </SOAP-ENV:Body>
</SOAP-ENV:Envelope>

<soapenv:Envelope
    xmlns:soapenv="http://schemas.xmlsoap.org/soap/envelope/"
    xmlns:ns="http://www.opensmartgridplatform.org/schemas/common/2014/10"
    xmlns:ns1="http://www.opensmartgridplatform.org/schemas/publiclighting/adhocmanagement/2014/10">
   <soapenv:Header>
      <ns:ApplicationName>SoapUI</ns:ApplicationName>
      <ns:UserName>Sander</ns:UserName>
      <ns:OrganisationIdentification>LianderNetManagement</ns:OrganisationIdentification>
   </soapenv:Header>
   <soapenv:Body>
      <ns1:SetLightAsyncRequest>
         <ns1:AsyncRequest>
            <ns:CorrelationUid>LianderNetManagement|||KAI-0000000053|||20180925093054301</ns:CorrelationUid>
            <ns:DeviceId>KAI-0000000053</ns:DeviceId>
         </ns1:AsyncRequest>
      </ns1:SetLightAsyncRequest>
   </soapenv:Body>
</soapenv:Envelope>

<SOAP-ENV:Envelope
    xmlns:SOAP-ENV="http://schemas.xmlsoap.org/soap/envelope/">
   <SOAP-ENV:Header/>
   <SOAP-ENV:Body>
      <ns2:SetLightResponse
          xmlns:ns2="http://www.opensmartgridplatform.org/schemas/publiclighting/adhocmanagement/2014/10"
          xmlns:ns3="http://www.opensmartgridplatform.org/schemas/common/2014/10">
         <ns2:Result>OK</ns2:Result>
      </ns2:SetLightResponse>
   </SOAP-ENV:Body>
</SOAP-ENV:Envelope>
```

IEC61850 platform message of the data set on the device:

```javascript
LogicalDevice: SWDeviceGenericIO
messageType: SetLight {
  XSWC2.Pos[CO].Oper.ctlVal: true
  XSWC3.Pos[CO].Oper.ctlVal: true
}
```

IEC61850 protocol adapter logging:

```
2018-09-25 09:30:54.775] [osgp-tst-03] [iec61850RequestsMessageListenerContainer-11] INFO o.o.a.p.i.i.n.s.Iec61850SsldDeviceService@createListOfInternalIndicesToSwitch:220 - creating list of internal indices using device output settings
2018-09-25 09:30:54.782] [osgp-tst-03] [iec61850RequestsMessageListenerContainer-11] INFO o.o.a.p.i.i.n.s.c.Iec61850SetLightCommand@apply:66 - Trying to switch light relay with internal index: 2 on: true for device: KAI-0000000053
2018-09-25 09:30:54.783] [osgp-tst-03] [iec61850RequestsMessageListenerContainer-11] INFO o.o.a.p.i.i.n.h.DeviceConnection@createObjectReference:94 - Device: KAI-0000000053, ObjectReference: SWDeviceGenericIO/XSWC2.CfSt
2018-09-25 09:30:54.799] [osgp-tst-03] [iec61850RequestsMessageListenerContainer-11] INFO o.o.a.p.i.i.n.s.c.Iec61850Commands@enableOperationOfRelay:56 - masterControl.enbOper is true, switching of relay 2 is enabled
2018-09-25 09:30:54.852] [osgp-tst-03] [iec61850RequestsMessageListenerContainer-11] INFO o.o.a.p.i.i.n.h.DeviceConnection@createObjectReference:94 - Device: KAI-0000000053, ObjectReference: SWDeviceGenericIO/XSWC2.Pos
2018-09-25 09:30:54.881] [osgp-tst-03] [iec61850RequestsMessageListenerContainer-11] INFO o.o.a.p.i.i.n.s.c.Iec61850SetLightCommand@switchLightRelay:108 - Switching relay 2 on
2018-09-25 09:30:54.898] [osgp-tst-03] [iec61850RequestsMessageListenerContainer-11] INFO o.o.a.p.i.i.n.s.c.Iec61850SetLightCommand@apply:66 - Trying to switch light relay with internal index: 3 on: true for device: KAI-0000000053
2018-09-25 09:30:54.898] [osgp-tst-03] [iec61850RequestsMessageListenerContainer-11] INFO o.o.a.p.i.i.n.h.DeviceConnection@createObjectReference:94 - Device: KAI-0000000053, ObjectReference: SWDeviceGenericIO/XSWC3.CfSt
2018-09-25 09:30:54.986] [osgp-tst-03] [iec61850RequestsMessageListenerContainer-11] INFO o.o.a.p.i.i.n.s.c.Iec61850Commands@enableOperationOfRelay:56 - masterControl.enbOper is true, switching of relay 3 is enabled
2018-09-25 09:30:54.986] [osgp-tst-03] [iec61850RequestsMessageListenerContainer-11] INFO o.o.a.p.i.i.n.h.DeviceConnection@createObjectReference:94 - Device: KAI-0000000053, ObjectReference: SWDeviceGenericIO/XSWC3.Pos
2018-09-25 09:30:55.211] [osgp-tst-03] [iec61850RequestsMessageListenerContainer-11] INFO o.o.a.p.i.i.n.s.c.Iec61850SetLightCommand@switchLightRelay:108 - Switching relay 3 on
2018-09-25 09:30:55.553] [osgp-tst-03] [iec61850RequestsMessageListenerContainer-11] INFO o.o.a.p.i.s.DeviceMessageLoggingService@logMessage:52 - Sending iec61850LogItemRequestMessage for device: KAI-0000000053
2018-09-25 09:30:55.554] [osgp-tst-03] [iec61850RequestsMessageListenerContainer-11] INFO o.o.a.p.i.s.DeviceResponseService@handleDeviceMessageStatus:42 - OK device message status received: OK
```


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation dynamically by asking a question.

Perform an HTTP GET request on the current page URL with the `ask` query parameter, and the optional `goal` query parameter:

```
GET https://grid-exchange-fabric.gitbook.io/gxf/protocols/iec61850/swdevice-010805/setlight.md?ask=<question>&goal=<endgoal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is optional and describes the broader end goal you are ultimately trying to accomplish on behalf of the user. GitBook uses it to tailor the answer towards what is most useful for that goal.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.