FlexOVL_540_171101_2_out.icd
<?xml version="1.0" encoding="utf-8"?>
<!--Generated with ABB IEC61850 Libraries 5.3.1.25 at 1-11-2017 15:05:17.-->
<SCL xmlns="http://www.iec.ch/61850/2003/SCL" xmlns:sxy="http://www.iec.ch/61850/2003/SCLcoordinates" xmlns:esld="http://www.abb.com/61850/2006/SCL_SLD" xmlns:eComm="http://www.abb.com/61850/2009/SCL_ABBCommunication" xmlns:eABB="http://www.abb.com/61850/2010/ABBTranslations" xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:schemaLocation="http://www.iec.ch/61850/2003/SCL SCL.xsd http://www.iec.ch/61850/2003/SCLcoordinates SCL_Coordinates.xsd http://www.abb.com/61850/2006/SCL_SLD SCL_SLD.xsd http://www.abb.com/61850/2009/SCL_ABBCommunication SCL_ABBCommunication.xsd http://www.abb.com/61850/2010/ABBTranslations SCL_ABBTranslations.xsd">
<Private type="ABB SLD">
<esld:SLD>
<esld:Sizes elementSize="1" />
<esld:AlarmSettings />
<esld:MeasurementStatus />
<esld:DefaultColors />
<esld:NameDisplay />
<esld:Fonts />
<esld:MeasurementPrecision defaultDecimals="0" />
<esld:DisplayMultipliers />
</esld:SLD>
<esld:BusbarColoring triggeringTimeBuffer="0" />
</Private>
<Header id="ID" version="2003" revision="A" nameStructure="IEDName" />
<Communication>
<SubNetwork name="WA1" desc="Subnetwork" type="8-MMS">
<Private type="ABBPCMInternalObjRef">fe64bc9f-6918-4694-b3c7-b8f84dede770</Private>
<ConnectedAP iedName="AA1TH01" apName="S1">
<Address>
<P type="IP" xsi:type="tP_IP">192.168.0.10</P>
<P type="OSI-AP-Title" xsi:type="tP_OSI-AP-Title">1,3,9999,23</P>
<P type="OSI-AE-Qualifier" xsi:type="tP_OSI-AE-Qualifier">23</P>
<P type="OSI-PSEL" xsi:type="tP_OSI-PSEL">00000001</P>
<P type="OSI-SSEL" xsi:type="tP_OSI-SSEL">0001</P>
<P type="OSI-TSEL" xsi:type="tP_OSI-TSEL">0001</P>
<P type="IP-GATEWAY" xsi:type="tP_IP-GATEWAY">0.0.0.0</P>
<P type="IP-SUBNET" xsi:type="tP_IP-SUBNET">255.255.255.0</P>
</Address>
</ConnectedAP>
</SubNetwork>
</Communication>
<IED name="AA1TH01" desc="Server" type="RTU560_2" manufacturer="ABB" configVersion="1.3">
<Private type="ABB_PCMObjectTypeName">Generic IEC61850 IED</Private>
<Private type="ABBPCMInternalObjRef">580da69c-6a72-4d9d-8a28-0978d0d82a5b</Private>
<Services>
<DynAssociation />
<GetDirectory />
<GetDataObjectDefinition />
<DataObjectDirectory />
<GetDataSetValue />
<DataSetDirectory />
<ConfDataSet max="48" maxAttributes="450" />
<ReadWrite />
<ConfReportControl max="48" />
<GetCBValues />
<ReportSettings cbName="Conf" datSet="Conf" rptID="Dyn" optFields="Dyn" bufTime="Dyn" trgOps="Dyn" intgPd="Dyn" />
<GSESettings cbName="Conf" datSet="Conf" appID="Conf" />
<GOOSE max="8" />
<ConfLNs fixPrefix="true" fixLnInst="true" />
</Services>
<AccessPoint name="S1">
<Server>
<Authentication />
<LDevice inst="LD0">
<LN0 lnClass="LLN0" inst="" lnType="LLN0_RTU560_2_IEC61850">
<DataSet name="StatNrmlA" desc="Status data used for event list entries.">
<FCDA ldInst="LD0" lnClass="LPHD" lnInst="1" doName="PhyHealth" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="1" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="9" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="7" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="2" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="3" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="5" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="16" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="15" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="14" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="13" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="12" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="11" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="10" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="4" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="6" doName="Ind" fc="ST" />
<FCDA ldInst="LD0" prefix="SP" lnClass="GGIO" lnInst="8" doName="Ind" fc="ST" />
</DataSet>
<ReportControl name="rcb_A" rptID="A" datSet="StatNrmlA" confRev="1" bufTime="500" buffered="true">
<TrgOps dchg="true" qchg="true" />
<OptFields />
</ReportControl>
<DOI name="NamPlt">
<DAI name="swRev">
<Val>12.0.3.0</Val>
</DAI>
</DOI>
</LN0>
<LN lnClass="LPHD" inst="1" lnType="LPHD_RTU560_2_IEC61850">
<DOI name="PhyNam">
<DAI name="swRev">
<Val>12.0.3.0</Val>
</DAI>
</DOI>
<DOI name="PhyHealth" desc="IED operable">
<DAI name="stVal">
<Private type="RTU560_IED_Health">1000</Private>
</DAI>
</DOI>
</LN>
<LN prefix="SP" lnClass="GGIO" inst="1" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="9" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="7" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="2" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="3" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="5" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="16" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="15" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="14" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="13" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="12" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="11" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="10" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="4" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="6" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
<LN prefix="SP" lnClass="GGIO" inst="8" lnType="ABBRTU500_2_Rev1_SPGGIO_#LIB1" />
</LDevice>
</Server>
</AccessPoint>
</IED>
<DataTypeTemplates>
<LNodeType id="LLN0_RTU560_2_IEC61850" lnClass="LLN0" iedType="RTU560_2">
<DO name="Mod" type="tcROMod_RTU560_2_IEC61850" />
<DO name="Beh" type="tcBeh_RTU560_2_IEC61850" />
<DO name="Health" type="tcHealth_RTU560_2_IEC61850" />
<DO name="NamPlt" type="tcLPL_LLN0_RTU560_2_IEC61850" />
<DO name="Loc" type="tcSPS_RTU560_2_IEC61850" />
</LNodeType>
<LNodeType id="LPHD_RTU560_2_IEC61850" lnClass="LPHD" iedType="RTU560_2">
<DO name="PhyNam" type="tcDPL_RTU560_2_IEC61850" />
<DO name="PhyHealth" type="tcHealth_RTU560_2_IEC61850" />
<DO name="Proxy" type="tcSPS_RTU560_2_IEC61850" />
</LNodeType>
<LNodeType id="ABBRTU500_2_Rev1_SPGGIO_#LIB1" lnClass="GGIO" iedType="RTU560_2">
<DO name="Mod" type="ABBRTU500_2_Rev1_tcROMod" />
<DO name="Beh" type="ABBRTU500_2_Rev1_tcBeh" />
<DO name="Health" type="ABBRTU500_2_Rev1_tcHealth" />
<DO name="NamPlt" type="ABBRTU500_2_Rev1_tcLPL_#LIB1" />
<DO name="Ind" type="ABBRTU500_2_Rev1_tcSPS" />
</LNodeType>
<DOType id="tcROMod_RTU560_2_IEC61850" cdc="INC" iedType="RTU560_2">
<DA name="stVal" bType="Enum" valKind="RO" type="Mod" fc="ST" dchg="true">
<Val>on</Val>
</DA>
<DA name="q" bType="Quality" valKind="RO" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" valKind="RO" fc="ST" />
<DA name="ctlModel" bType="Enum" valKind="RO" type="ctlModel" fc="CF">
<Val>status-only</Val>
</DA>
<DA name="d" bType="VisString255" fc="DC" />
</DOType>
<DOType id="tcBeh_RTU560_2_IEC61850" cdc="INS" iedType="RTU560_2">
<DA name="stVal" bType="Enum" valKind="RO" type="Beh" fc="ST" dchg="true">
<Val>on</Val>
</DA>
<DA name="q" bType="Quality" valKind="RO" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" valKind="RO" fc="ST" />
<DA name="d" bType="VisString255" fc="DC" />
</DOType>
<DOType id="tcHealth_RTU560_2_IEC61850" cdc="INS" iedType="RTU560_2">
<DA name="stVal" bType="Enum" type="Health" fc="ST" dchg="true">
<Val>Alarm</Val>
</DA>
<DA name="q" bType="Quality" valKind="RO" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" valKind="RO" fc="ST" />
<DA name="d" bType="VisString255" fc="DC" />
</DOType>
<DOType id="tcLPL_LLN0_RTU560_2_IEC61850" cdc="LPL" iedType="RTU560_2">
<DA name="vendor" bType="VisString255" valKind="RO" fc="DC">
<Val>ABB</Val>
</DA>
<DA name="swRev" bType="VisString255" fc="DC">
<Val>11.4.2.0</Val>
</DA>
<DA name="d" bType="VisString255" valKind="RO" fc="DC">
<Val>RTU560_Server</Val>
</DA>
<DA name="configRev" bType="VisString255" fc="DC">
<Val>1</Val>
</DA>
<DA name="ldNs" bType="VisString255" fc="EX">
<Val>IEC 61850-7-4:2003</Val>
</DA>
</DOType>
<DOType id="tcSPS_RTU560_2_IEC61850" cdc="SPS" iedType="RTU560_2">
<DA name="stVal" bType="BOOLEAN" fc="ST" dchg="true">
<Val>false</Val>
</DA>
<DA name="q" bType="Quality" valKind="RO" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" valKind="RO" fc="ST" />
<DA name="d" bType="VisString255" fc="DC" />
</DOType>
<DOType id="tcDPL_RTU560_2_IEC61850" cdc="DPL" iedType="RTU560_2">
<DA name="vendor" bType="VisString255" valKind="RO" fc="DC">
<Val>ABB</Val>
</DA>
<DA name="swRev" bType="VisString255" fc="DC">
<Val>11.4.2.0</Val>
</DA>
<DA name="serNum" bType="VisString255" fc="DC" />
<DA name="model" bType="VisString255" valKind="RO" fc="DC">
<Val>RTU560_Server</Val>
</DA>
</DOType>
<DOType id="ABBRTU500_2_Rev1_tcROMod" cdc="INC" iedType="RTU560_2">
<DA name="stVal" bType="Enum" valKind="RO" type="Mod" fc="ST" dchg="true">
<Val>on</Val>
</DA>
<DA name="q" bType="Quality" valKind="RO" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" valKind="RO" fc="ST" />
<DA name="ctlModel" bType="Enum" valKind="RO" type="ctlModel" fc="CF">
<Val>status-only</Val>
</DA>
<DA name="d" bType="VisString255" fc="DC" />
</DOType>
<DOType id="ABBRTU500_2_Rev1_tcBeh" cdc="INS" iedType="RTU560_2">
<DA name="stVal" bType="Enum" valKind="RO" type="Beh" fc="ST" dchg="true">
<Val>on</Val>
</DA>
<DA name="q" bType="Quality" valKind="RO" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" valKind="RO" fc="ST" />
<DA name="d" bType="VisString255" fc="DC" />
</DOType>
<DOType id="ABBRTU500_2_Rev1_tcHealth" cdc="INS" iedType="RTU560_2">
<DA name="stVal" bType="Enum" type="Health" fc="ST" dchg="true">
<Val>Alarm</Val>
</DA>
<DA name="q" bType="Quality" valKind="RO" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" valKind="RO" fc="ST" />
<DA name="d" bType="VisString255" fc="DC" />
</DOType>
<DOType id="ABBRTU500_2_Rev1_tcLPL_#LIB1" cdc="LPL" iedType="RTU560_2">
<DA name="vendor" bType="VisString255" valKind="RO" fc="DC">
<Val>ABB</Val>
</DA>
<DA name="swRev" bType="VisString255" fc="DC">
<Val>12.0.3.0</Val>
</DA>
<DA name="d" bType="VisString255" valKind="RO" fc="DC">
<Val>RTU560_Server</Val>
</DA>
<DA name="configRev" bType="VisString255" fc="DC">
<Val>1</Val>
</DA>
</DOType>
<DOType id="ABBRTU500_2_Rev1_tcSPS" cdc="SPS" iedType="RTU560_2">
<DA name="stVal" bType="BOOLEAN" fc="ST" dchg="true">
<Val>false</Val>
</DA>
<DA name="q" bType="Quality" valKind="RO" fc="ST" qchg="true" />
<DA name="t" bType="Timestamp" valKind="RO" fc="ST" />
<DA name="d" bType="VisString255" fc="DC" />
</DOType>
<EnumType id="Mod">
<EnumVal ord="1">on</EnumVal>
<EnumVal ord="2">blocked</EnumVal>
<EnumVal ord="3">test</EnumVal>
<EnumVal ord="4">test/blocked</EnumVal>
<EnumVal ord="5">off</EnumVal>
</EnumType>
<EnumType id="ctlModel">
<EnumVal ord="0">status-only</EnumVal>
<EnumVal ord="1">direct-with-normal-security</EnumVal>
<EnumVal ord="2">sbo-with-normal-security</EnumVal>
<EnumVal ord="3">direct-with-enhanced-security</EnumVal>
<EnumVal ord="4">sbo-with-enhanced-security</EnumVal>
</EnumType>
<EnumType id="Beh">
<EnumVal ord="1">on</EnumVal>
<EnumVal ord="2">blocked</EnumVal>
<EnumVal ord="3">test</EnumVal>
<EnumVal ord="4">test/blocked</EnumVal>
<EnumVal ord="5">off</EnumVal>
</EnumType>
<EnumType id="Health">
<EnumVal ord="1">Ok</EnumVal>
<EnumVal ord="2">Warning</EnumVal>
<EnumVal ord="3">Alarm</EnumVal>
</EnumType>
</DataTypeTemplates>
</SCL>
Last updated