This covers the services for tariff switching domain using the open smart grid platform.
This domain allows tariff switching. It allows a relay to switch when a tariff changes. This domain could be used to replace ripple control tariff signals.
When configuring a device via the platform to switch relays according to a tariff schedule, the device can be instructed to switch the tariff relay normally ("TARIFF") or reversed ("TARIFF_REVERSED").
The devices themselves are unaware of the difference between TARIFF and TARIFF_REVERSED. When sending a setScheduleRequest message for a tariff schedule to the platform, the tariff switching domain adapter checks if the device relay(s) are configured with TARIFF_REVERSED. If so, the tariff switching domain adapter will invert the relay value for all tariff schedule entries before the tariff schedule is sent to the device.
When two devices have the same schedule, while one device is using TARIFF and the other TARIFF_REVERSED, the state of their tariff relays will always be the opposite of each other.
The values as shown in the table below will be returned, when getting the status from a device or from the platform.
Operation
Request
Response
TariffSwitchingAdHocManagement.wsdl
GetDevices
GetStatus
DeviceIdentification
Status
TariffSwitchingScheduleManagement.wsdl
SetSchedule
DeviceIdentification, Schedules, Page
-
Type
State
Relay powered
Returned by Device
Returned by Platform
TARIFF
LOW
yes
on = true
High = false
HIGH
no
on = false
High = true
TARIFF_REVERSED
LOW
no
on = false
High = false
HIGH
yes
on = true
High = true